Svyaz Inzhiniring SIPB10KD.9-11 UPS: battery charge reads 0% via SNMP web interface while display shows it correctly
What happened
The UPS display showed a plausible battery charge percentage, while the web interface through the SNMP card read 0%; all other reported values matched. As also reported in the case, units of the same manufacturer had suffered lost controller settings, including the configured battery count, which drove charge voltage too high and destroyed battery banks.
What was checked
- The engineers compared the battery readings on the display with the values coming through the SNMP card web interface to confirm that only the charge figure was wrong.
- They went through how the controller settings, including the battery count, had been entered and saved — from a program or from the panel — and whether they survived a reboot; in this case they did not.
Cause
A software fault in the unit: the controller lost its settings, so the configured battery count ended up higher than the real bank and the batteries were charged at excessive voltage. The manufacturer did not explain the root cause of the failure.
What was done
As reported in the case, three units were replaced under warranty before the problem stopped recurring. In the end, a different model in a similar enclosure was installed together with a battery block containing the maximum number of batteries, so that even if the battery-count setting failed again it could not push the charge voltage above the safe limit for the bank.
Safety
A UPS battery bank stores enough energy to cause severe arc flash: isolate the unit before any work, treat DC battery terminals as live at all times, and before return to use verify the configured battery count and charge voltage against the actual bank and complete the manufacturer's electrical safety checks.
Lesson: When a controller can silently lose critical settings, configure the hardware so the worst-case wrong setting cannot damage the batteries, and re-verify the battery configuration after every reboot or firmware fault.
Covered in the course: Power and Cooling for Medical Equipment — Level 2: Fault-Finding →
Written from an anonymised case shared by service engineers. It is not a manufacturer instruction and grants no authorisation. Independent note; names are trademarks of their owners.