Tescom DS300: repeated IGBT faults lock out the inverter
What happened
Reported in the case: the UPS logged an IGBT fault four times within thirty minutes and locked the inverter out. On inspection, one of the six power chokes ran hot with visible burn on its insulation.
What was checked
- The engineers inspected the power chokes: one of the six ran noticeably hot and showed burned insulation.
- The engineers inspected the IGBT module for damage consistent with the repeated fault trips.
- The load was transferred to bypass so it stayed supplied while the inverter side was checked.
Cause
Probable cause: the burned power choke degraded the inverter stage and caused the IGBT failure. The engineers assessed this as probable, matching a comparable case where the same fault pattern was cleared by replacing the choke together with the IGBT set and control boards.
The cause is probable and was not fully confirmed.
What was done
The engineers replaced the burned choke and the complete IGBT set with its control boards, following the manufacturer's service documentation. Until the repair was completed, the MRI scanner ran on bypass as a temporary measure.
Safety
An inverter stage holds lethal stored energy: treat the DC bus capacitors as charged even after shutdown, verify discharge and isolation before opening the power section, and complete the manufacturer's electrical safety checks before returning the UPS to service.
Lesson: A repeated IGBT fault can be the symptom rather than the fault itself — inspect the passive power components around the inverter, such as chokes and bus connections, before condemning the switches.
Covered in the course: Power and Cooling for Medical Equipment — Level 2: Fault-Finding →
Written from an anonymised case shared by service engineers. It is not a manufacturer instruction and grants no authorisation. Independent note; names are trademarks of their owners.